3 / 4 page A05-0315-002 Wiring Guide System wiring diagram for 4-wire duct smoke detectors Wiring diagram for DH100ACDCI to SSK451 and interconnect feature: 15 19 14 3 20 1 3 2 Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power – NOTE: Wiring diagram shown is for DH100ACDCI 4-wire duct smoke detector system equipped without a control panel. Alarm Power Common APA451 DH100ACDCI NOTE: A trouble condition is indicated when the green LED is not illuminated. Important Interconnect Notes • When using the interconnect feature, all interconnected units must be powered with the same, independent supply. • Polarity must be maintained throughout the interconnect wiring. Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit 2 and so on. Wiring diagram for the DH100ACDCI to RTS451/ RTS451KEY and interconnect feature: COMMON 3 TEMPORAL SELECT 2 ALARM SIGNAL 1 SUPERVISORY SIGNAL 4 RESET 7 TEST 8 POWER (–) 6 POWER (+) 5 15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX. POWER (–) 19 AUX. POWER (+) 12 INTERCONNECT + 1 INTERCONNECT – SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACT NO 12 INTERCONNECT + 1 INTERCONNECT – DH100ACDCI UNIT 2 FIELD INSTALLED JUMPER DH100ACDCI UNIT 1 15 19 14 3 20 2 11 2 6 1 Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power – Reset Test (Red LED) Alarm (Green LED) Power 12 1 12 1 Interconnect + Unit 1 Interconnect – DH100ACDCI DH100ACDCI UNIT 2 RTS451/RTS451KEY 5 4 3 *NOTE: For RTS451KEY only without a Control Panel. RTS451 does not have a terminal 6. NOTE: Wiring diagram shown is for DH100ACDCI 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated. * Interconnect – Interconnect + Wiring diagram for DH100ACDCI to APA451: 24V 120 VAC 220/240 VAC 9 10 A B C AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 16 6 17 7 18 8 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. 24V 220/240 VAC 9 10 A B C AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 16 6 17 7 18 8 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. 14 3 3 14 4 5 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. 4 5 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. ALARM INITIATION LOOP UL LISTED 4-WIRE CONTROL PANEL FIRST DETECTOR IN THE LOOP DH100ACDCI LAST DETECTOR IN THE LOOP DH100ACDCI EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION. FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER. NOTE: THE SUPERVISORY RELAY NOW PROVIDES A "FORM C" CONTACT FOR CUSTOMIZED APPLICATIONS. FOR STANDARD APPLICATIONS, ONLY THE "NO" CONTACT IS USED POWER INPUTS ACCEPT 24 VDC, 24 VAC 50-60 HZ, 120 VAC 50-60 HZ, OR 220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. AUX. CONTACT RATINGS 10A @ 30 VDC RESISTIVE 10A @ 250 VAC 100mA MINIMUM @ 5 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS. TROUBLE CONTACT RATING 2.0 A @ 30 VDC resistive + – 120 VAC *NOTE: For RTS451KEY only without a Control Panel. RTS451 does not have a terminal 6. NOTE: Wiring diagram shown is for DH100ACDCLP 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated. Coil Note: Please note that the magnetic coil supplied with the RTS451/RTS451KEY is not required when these accessories are used with the DH100 detectors. The functionality of the magnetic coil has been designed into the circuitry of the Innovair duct smoke detectors. |
Ähnliche Teilenummer - ST-3 |
|
Ähnliche Beschreibung - ST-3 |
|
|
Link URL |
Privatsphäre und Datenschutz |
ALLDATASHEETDE.COM |
War ALLDATASHEET hilfreich? [ DONATE ] |
Über Alldatasheet | Werbung | Kontakt | Privatsphäre und Datenschutz | Linktausch | Hersteller All Rights Reserved©Alldatasheet.com |
Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
Family Site : ic2ic.com |
icmetro.com |