Datenblatt-Suchmaschine für elektronische Bauteile
Selected language     German  ▼
Bauteilbezeichnung
         Beschreibung


2702131 Datenblatt(Datasheet) 2 Page - PHOENIX CONTACT

Teile-Nr. 2702131
Beschreibung  EtherNet/IP™ bus coupler, extreme conditions version, 8 inputs 24 V DC, 4 outputs 24 V DC, 500 mA, complete with I/O connectors
Download  6 Pages
Scroll/Zoom Zoom In 100% Zoom Out
Hersteller  PHOENIX [PHOENIX CONTACT]
Homepage  http://www.phoenixcontact.com
Logo 

   
 2 page
background image
https://www.phoenixcontact.com/us/products/2702131
05/15/2015   Page 2 / 6
Bus coupler - IL EIP BK DI8 DO4 2TX-XC-PAC - 2702131
Technical data
Dimensions
Width
80 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Specfications with connectors
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
-40 °C ... 70 °C (See “Tested successfully: use under extreme ambient
conditions” in the data sheet.)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
Connection data
Designation
Inline connector
Connection method
Spring-cage connection
Conductor cross section solid min.
0.08 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.08 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
Stripping length
8 mm
General
Net weight
329 g
Note on weight specifications
with connectors
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B; 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN 61000-4-3/IEC 61000-4-3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN 61000-4-4/IEC 61000-4-4 Criterion A; all interfaces 1
kVCriterion B; all interfaces 2 kV




Html Pages

1  2  3  4  5  6 


Datasheet Download




Link URL

War ALLDATASHEET hilfreich?  [ Spenden ]  